     1= Servers =
     2
     3 ||  srv1.rrail.cosmos-lab.org  || !BubbleRan Master node    ||
     4 ||  srv2.rrail.cosmos-lab.org  || !BubbleRan Worker node 1  ||
     5 ||  srv1.rrail.cosmos-lab.org  || !BubbleRan Worker node 2  ||
     6 ||  srv1.rrail.cosmos-lab.org  || !BubbleRan Worker node 3  ||
     7 ||  srv1.rrail.cosmos-lab.org  || Log collection node (Grafana, InfluxDb, etc.) ||
     8 
     9
     10== PDU: pdu1-cr3.orbit-lab.org ==
     11
     12Sandbox1 servers srv1-lg1.sb1.cosmos-lab.org and srv2-lg1.sb1.cosmos-lab.org are connected to PDU in Core Rack 3  (pdu1-cr3.orbit-lab.org and pdu2-cr3.orbir-lab.org). The PDU is of type [https://www.servertech.com/power-distribution-unit-pdu/switched-pops-pdu/0u-vertical-2G16/stv-6521v STV-6521V] with the following characteristics:
     13
     14=== Measurement Accuracy ===
     15
     16==== Input Measurement Accuracy ====
     17LED Current = ± 10% at 0.1 amp (0.5 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
     18GUI Current = ± 1% at 0.01 amp resolution (above 0.5 amp)
     19Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
     20Active Power = ± 1% at 1 watt resolution
     21Apparent Power = ± 1% at 1 volt-amp resolution
     22Power Factor = ± 3% at 0.01 resolution
     23Crest Factor = ± 10% at 0.1 resolution
     24Energy = ± 1% at 0.1 kilowatt-hour resolution
     25
     26==== Output Measurement Accuracy ====
     27GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp)
     28Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
     29Active Power = ± 1% at 1 watt resolution
     30Apparent Power = ± 1% at 1 volt-amp resolution
     31Power Factor = ± 3% at 0.01 resolution
     32Crest Factor = ± 10% at 0.1 resolution
     33Energy = ± 1% at 1 watt-hour resolution
     34
     35==== Branch Measurement Accuracy ====
     36
     37Current = ± 3% at 0.01 amp resolution (above 0.5 amp)
     38