STV-6521V
Device Name: pdu1-cr3.orbit-lab.org
Sandbox1 servers srv1-lg1.sb1.cosmos-lab.org and srv2-lg1.sb1.cosmos-lab.org are connected to PDUs in Core Rack 3 (pdu1-cr3.orbit-lab.org and pdu2-cr3.orbir-lab.org). The PDU is of type STV-6521V with the following characteristics:
Measurement Accuracy
Input Measurement Accuracy
- LED Current = ± 10% at 0.1 amp (0.5 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
- GUI Current = ± 1% at 0.01 amp resolution (above 0.5 amp)
- Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
- Active Power = ± 1% at 1 watt resolution
- Apparent Power = ± 1% at 1 volt-amp resolution
- Power Factor = ± 3% at 0.01 resolution
- Crest Factor = ± 10% at 0.1 resolution
- Energy = ± 1% at 0.1 kilowatt-hour resolution
Output Measurement Accuracy
- GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp)
- Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
- Active Power = ± 1% at 1 watt resolution
- Apparent Power = ± 1% at 1 volt-amp resolution
- Power Factor = ± 3% at 0.01 resolution
- Crest Factor = ± 10% at 0.1 resolution
- Energy = ± 1% at 1 watt-hour resolution
Branch Measurement Accuracy
- Current = ± 3% at 0.01 amp resolution (above 0.5 amp)