[[Include(Internal/WikiToC)]] == ​STV-6521V Device Name: pdu1-cr3.orbit-lab.org Sandbox1 servers srv1-lg1.sb1.cosmos-lab.org and srv2-lg1.sb1.cosmos-lab.org are connected to PDU in Core Rack 3 (pdu1-cr3.orbit-lab.org and pdu2-cr3.orbir-lab.org). The PDU is of type [https://www.servertech.com/power-distribution-unit-pdu/switched-pops-pdu/0u-vertical-2G16/stv-6521v STV-6521V] with the following characteristics: === Measurement Accuracy === ==== Input Measurement Accuracy ==== * LED Current = ± 10% at 0.1 amp (0.5 - 9.9 amps) and 1 amp (> 9.9 amps) resolution * GUI Current = ± 1% at 0.01 amp resolution (above 0.5 amp) * Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%) * Active Power = ± 1% at 1 watt resolution * Apparent Power = ± 1% at 1 volt-amp resolution * Power Factor = ± 3% at 0.01 resolution * Crest Factor = ± 10% at 0.1 resolution * Energy = ± 1% at 0.1 kilowatt-hour resolution ==== Output Measurement Accuracy ==== * GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp) * Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%) * Active Power = ± 1% at 1 watt resolution * Apparent Power = ± 1% at 1 volt-amp resolution * Power Factor = ± 3% at 0.01 resolution * Crest Factor = ± 10% at 0.1 resolution * Energy = ± 1% at 1 watt-hour resolution ==== Branch Measurement Accuracy ==== * Current = ± 3% at 0.01 amp resolution (above 0.5 amp)