| 1 | == C3WG36RL == |
| 2 | |
| 3 | RRAIL servers srv1.rrail.cosmos-lab.org - srv5.rrail.cosmos-lab.org are connected to PDUs in Core Rack 2 (pdu1-cr2.orbit-lab.org and pdu2-cr2.orbir-lab.org). The PDUs are of type [https://www.servertech.com/power-distribution-unit-pdu/switched-pops-pdu/0u-vertical-3G01/c3wg36rl-2cje2mt4 C3WG36RL] with the following key characteristics: |
| 4 | |
| 5 | === Measurement Accuracy === |
| 6 | |
| 7 | ==== Input Measurement Accuracy ==== |
| 8 | |
| 9 | * LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution |
| 10 | * GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp) |
| 11 | * Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%) |
| 12 | * Active Power = ± 1% at 1 watt resolution |
| 13 | * Apparent Power = ± 1% at 1 volt-amp resolution |
| 14 | * Power Factor = ± 3% at 0.01 resolution |
| 15 | * Crest Factor = ± 10% at 0.1 resolution |
| 16 | * Energy = ± 1% at 0.1 kilowatt-hour resolution |
| 17 | |
| 18 | ==== Output Measurement Accuracy ==== |
| 19 | |
| 20 | * GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp) |
| 21 | * Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%) |
| 22 | * Active Power = ± 1% at 1 watt resolution |
| 23 | * Apparent Power = ± 1% at 1 volt-amp resolution |
| 24 | * Power Factor = ± 3% at 0.01 resolution |
| 25 | * Crest Factor = ± 10% at 0.1 resolution |
| 26 | * Energy = ± 1% at 1 watt-hour resolution |